Components of a Control Loop
A controller seeks to maintain the measured process variable (PV) at set
point (SP) in spite of unmeasured disturbances (D). The major components of
a control system include a sensor, a controller and a final control element.
To design and implement a controller, we must:
·
have identified a process variable we seek to regulate, be able to measure
it (or something directly related to it) with a sensor, and be able to
transmit that measurement as an electrical signal back to our controller,
and
·
have a final control element (FCE) that can receive the controller output
(CO) signal, react in some fashion to impact the process (e.g., a valve
moves), and as a result cause the process variable to respond in a consistent and
predictable fashion.
Home Temperature Control
As shown below (click
for a large view), the home heating control system
described in this article
can be organized as a traditional control loop block diagram. Block diagrams
help us visualize the components of a loop and see how the pieces are
connected.
A home heating system is simple on/off control with many of the
components contained in a small box mounted on our wall. Nevertheless, we
introduce the idea of control loop diagrams by presenting a home heating
system in the same way we would a more sophisticated commercial control
application.

Starting from the far right in the diagram above, our process variable of
interest is house temperature. A sensor, such as a
thermistor in a modern digital thermostat, measures temperature and
transmits a signal to the controller.
The measured temperature PV signal is subtracted
from set point to compute controller error, e(t) = SP
-
PV. The action of the controller is based on this error, e(t).
In our
home heating system,
the controller output (CO) signal is limited to open/close for the fuel flow
solenoid
valve (our FCE). So in this example, if e(t) = SP – PV > 0, the
controller signals to open
the valve. If e(t) = SP – PV < 0, it signals to close the valve. As an
aside, note that there
also must be a safety interlock to ensure that the furnace burner switches
on and off as the fuel flow valve opens and closes.
As the energy output of the furnace rises or falls, the
temperature of our house increases or decreases and a feedback loop is
complete. The important elements of a home heating control system can be organized
like any commercial application:
▪ Control Objective: maintain house temperature at SP in spite of
disturbances
▪ Process Variable: house temperature
▪ Measurement Sensor:
thermistor; or bimetallic strip coil on analog models
▪ Measured Process Variable (PV) Signal: signal transmitted from the
thermistor
▪ Set Point (SP): desired house temperature
▪ Controller Output (CO): signal to fuel valve actuator and furnace
burner
▪ Final Control Element (FCE): solenoid valve for fuel flow to furnace
▪ Manipulated Variable: fuel flow rate to furnace
▪ Disturbances (D): heat loss from doors, walls and windows; changing
outdoor temperature; sunrise and sunset; rain...
A General Control Loop and Intermediate Value Control
The home heating control loop above can be generalized into a block
diagram pertinent to all feedback control loops as shown below (click
for a large view).

Both diagrams above show a closed loop system based on negative feedback. That
is, the controller takes actions that counteract or oppose any drift in the
measured PV signal from set point.
While the home heating system is on/off, our focus going forward shifts
to intermediate value control loops. An intermediate value controller can
generate a full range of CO signals anywhere between full on/off or
open/closed. The
PI algorithm and
PID algorithm are examples of popular intermediate value controllers.
To implement intermediate value control, we require a sensor that can
measure a full range of our process variable, and a final control
element that can receive and assume a full range of intermediate positions
between full on/off or open/closed. This might include, for example, a process valve,
variable speed pump or compressor, or heating or cooling element.
Note from the loop diagram that the process variable becomes our official
PV only after it has been measured by a sensor and transmitted as an
electrical signal to the controller. In industrial applications. these are
most often implemented as 4-20 milliamps signals, though commercial
instruments are available that have been calibrated in a host of amperage
and voltage units.
With the loop closed as shown in the diagrams, we are said to be in
automatic mode and the controller is making all adjustments to the FCE. If
we were to open the loop and switch to manual mode, then we would be able to
issue CO commands through buttons or a keyboard directly to the FCE. Hence:
· open loop = manual mode
· closed loop = automatic mode
Cruise Control and Measuring Our PV
Cruise control in a car is a reasonably common intermediate value
control system. For those who are unfamiliar with cruise control, here is how
it works.
We first enable the control system with a button on the car instrument
panel. Once on the open road and at our desired cruising speed, we press a
second button that switches the controller from manual mode (where car speed
is adjusted by our foot) to automatic mode (where car speed is adjusted by
the controller).
The speed of the car at the moment we close the loop and switch from
manual to automatic becomes the set point. The
controller then continually computes and transmits corrective actions to the gas
pedal (throttle) to maintain measured speed at set point.
It is often cheaper and easier to measure and control a variable directly
related to the process variable of interest. This idea is central to control
system design and maintenance. And this is why the loop diagrams above
distinguish between our "process variable" and our "measured PV signal."
Cruise control serves to illustrate this idea. Actual car speed is
challenging to measure. But transmission rotational speed can be measured
reliably and inexpensively. The transmission connects the engine to the
wheels, so as it spins faster or slower, the car speed directly increases
or decreases.
Thus, we attach a small magnet to the rotating output shaft of the car
transmission and a magnetic field detector (loops of wire and a
simple circuit) to the body of the car above the magnet. With each rotation,
the magnet passes by the detector and the event is registered by the
circuitry as a “click.” As the drive shaft spins faster or slower, the click
rate and car speed increase or decrease proportionally.
So a cruise control system really adjusts fuel flow rate to maintain click
rate at the set point value. With this knowledge, we can organize cruise control
into the essential design elements:
▪ Control Objective: maintain car speed at SP in spite of
disturbances
▪ Process Variable: car speed
▪ Measurement Sensor:
magnet and coil to clock drive shaft rotation
▪ Measured Process Variable (PV) Signal: "click rate" signal from the
magnet and coil
▪ Set Point (SP): desired car speed, recast in the controller as a
desired click rate
▪ Controller Output (CO): signal to actuator that adjusts gas pedal
(throttle)
▪ Final Control Element (FCE): gas pedal position
▪ Manipulated Variable: fuel flow rate
▪ Disturbances (D): hills, wind, curves, passing trucks…
The traditional block diagram for cruise control (click
for a large view) is thus:

Instruments Should be Fast, Cheap and Easy
The above magnet and coil "click rate = car speed" example introduces
the idea that when purchasing an instrument for process control, there are
wider considerations that can make a loop faster, easier and cheaper to implement and
maintain. Here is a
"best practice" checklist to use when considering an instrument
purchase:
▪ Low cost
▪ Easy to install and wire
▪ Compatible with existing instrument interface
▪ Low maintenance
▪ Rugged and robust
▪ Reliable and long lasting
▪ Sufficiently accurate and precise
▪ Fast to respond (small time constant and dead time)
▪ Consistent with similar instrumentation already in the plant