Our control objective for the jacketed stirred reactor is to maintain reactor exit stream
temperature at set point in spite of disturbances caused by a changing
cooling liquid temperature entering the
vessel jacket.
In previous articles, we have established the
design level of operation for the reactor and explored the performance
of a single loop
PI controller and a
PID with CO Filter controller in meeting our control objective.
We
also have proposed a
cascade control architecture for the reactor that
offers potential for improving disturbance rejection
performance. We now apply our proposed architecture following the
implementation recipe for cascade control. Our goal is to demonstrate
the implementation procedure, understand the benefits and drawbacks of the
method, and explore cascade disturbance
rejection performance for this process.
The Reactor Cascade Control Architecture
The reactor cascade architecture has been
detailed in a previous article and is shown in the graphic below (click for a large view):

where:
CO2 = controller output to valve that adjusts cooling jacket liquid flow rate
(%)
PV2 = cooling jacket outlet temperature is our "early warning"
process variable (oC)
SP2 = CO1 = desired cooling jacket outlet temperature (oC)
PV1 = reactor exit stream temperature (oC)
SP1 = desired reactor exit stream temperature (oC)
D
= temperature of cooling liquid entering the jacket (oC)
Design Level of Operation (DLO)
The details and discussion for our DLO are
presented in this article and are summarized:
▪ Design PV1 and SP1 = 90 oC with approval for brief dynamic testing
of
±2 oC
▪ Design D = 43 oC with occasional spikes up to 50 oC
Minimum Criteria for Success
A
successful cascade implementation requires that early warning
process variable PV2 respond before outer primary PV1 both to changes
in the jacket cooling liquid temperature disturbance (D)
and to
changes in inner secondary controller output signal CO2. The plots below (click for a large view)
verify that both of these criteria are met with the architecture
shown in the graphic above.

Expressed concisely, the plots show that the delay in response (or
dead time,
Өp) follows the
rule:
Өp
(D
®
PV2) < Өp
(D
®
PV1) and Өp
(CO2 ®
PV2) < Өp
(CO2 ®
PV1)
Thus, a cascade control architecture should improve disturbance
rejection performance relative to a single loop architecture.
P-Only vs. PI for Inner Secondary Controller
The cascade implementation recipe first helps us decide if the inner secondary controller is
fast enough for a PI algorithm or if it is better suited for a P-Only algorithm.
The decision is based on the size of the inner secondary time
constant relative to that of the overall process time constant.
To compute these time constants, we need to
bump the process and analyze the dynamic process response data. In this
example we choose to place both inner secondary and outer primary
controllers in manual mode (open loop) during the bump test. An alternative
not explored here is to have the inner secondary controller in automatic
mode with
tuning
sufficiently
active to force a clear dynamic response in PV2.
Following the steps of the
cascade
implementation recipe:
1) With the process steady at the
design level of operation (DLO),
we perform a
doublet
test, choosing here to move CO2 from 34.3% ®
39.3% ® 29.3% ®
34.3%. We record both PV2 and PV1 dynamic data as the process responds. We
use this "step 1 data set" as we proceed with the implementation recipe.
2) As shown in the plots below, we use
commercial software to fit a first order plus dead time (FOPDT) model to the inner secondary process (CO2
® PV2)
dynamic data and another to the overall process (CO2
® PV1)
dynamic data (click
for a large view):

The FOPDT model parameters from these bump tests are summarized:
| |
Inner
Secondary
(CO2
® PV2) |
Overall Process
(CO2
® PV1) |
| Process
gain, Kp = |
– 0.57 °C/% |
–
0.51 °C/% |
| Time
constant, Tp = |
2.3 min |
2.2 min |
|
Dead
time, Өp
= |
0.25 min |
0.81 min |
The
cascade block diagram implies that the time constant and dead time values for the inner
process are contained within and contribute to the dynamics of the overall
process. Thus, we can surmise that:
Tp
(CO2
® PV2) ≤
Tp
(CO2
® PV1)
and Өp
(CO2
® PV2) ≤
Өp
(CO2
® PV1)
Yet the values in the table above indicate
that this seemingly fundamental relationship does not hold true for the
jacketed stirred reactor. In fact, when using a FOPDT model approximation of the dynamic
response data, the time constant of the inner secondary process
is slightly larger (longer) than that of the overall process.
The process graphic at the top of this
article shows a main reactor vessel
with a large
volume of liquid relative to that of the cooling jacket. The function of the
cooling jacket is to remove heat energy to regulate reactor vessel temperature. It seems logical
that because of the
volume differences, as long
as the liquid temperature in the large reactor is changing, the temperature
of the liquid in the
small cooling jacket must follow. And the liquid in the reactor acts as a
heat source
because the
chemical reaction inside the vessel generates heat energy faster as
reactor temperature rises (and vice versa).
This intertwined relationship of heat
generation and removal combined with relative sizes of the reactor and
jacket offers one physical
rationalization as to why the jacket (inner secondary) Tp might
reasonably be longer than that of the vessel (overall process) Tp.
A simpler explanation is that the sensor
used to measure temperature in the cooling jacket outlet flow was improperly
specified at the time of purchase, and unfortunately, it responds slowly to actual cooling liquid changes. This
additional response time alone could account for the observed behavior.
In any case, the dead time of the overall
process is three times that of the inner secondary
controller, and thus, PV2 provides a clear early warning that we can
exploit for a cascade design. So while the simple cascade
recipe has limitations that require our judgment, it provides valuable insights that
enable us to proceed.
3)
The
cascade implementation recipe
uses a time constant comparison to decide whether the inner secondary loop
is fast enough for a PI controller. We reach a true statement with case 1 of
the decision tree in step 3 of the recipe. That decision is:
if 3×Tp
(CO2 ®
PV2) > Tp (CO2 ®
PV1) => Use P-Only controller
or using the parameters in the table
above:
if 3(2.3 min)
> 2.2 min => Use a P-Only controller
Inner Secondary Controller
4) Our cascade implementation recipe states that a P-Only algorithm is the best choice for
the inner secondary controller. To explore this decision, we run four trials
and compare P-Only and PI algorithms side-by-side. We are able to use the same
"step 1
data set" for the design and tuning of all four of these inner secondary controllers:
TRIAL 1: moderate P-Only
TRIAL
2: aggressive P-Only
TRIAL
3: moderate PI
TRIAL
4: aggressive PI
As listed in the table in step 2 above, a
first order plus dead time (FOPDT) model fit of the "step 1 data set"
collected around our design level of operation (DLO) yields inner secondary
FOPDT model parameters:
CO2 ®
PV2 model: Kp = – 0.57 °C/%; Tp = 2.3
min; Өp
= 0.25 min
Following our
controller design and tuning recipe, we use these FOPDT model parameters
in rules and correlations to complete the secondary controller design.
P-Only Controller design and tuning, including the use of the ITAE tuning correlation
for computing controller gain, Kc, from FOPDT model parameters is
summarized in the example in this article. Following those details:
| P-Only algorithm:
|
CO = CObias
+ Kc∙e(t) |
TRIAL
1: Moderate P-Only

TRIAL
2: Aggressive P-Only
Kc = 2.5 (Moderate Kc) =
2.5 (–5.3) = –
13.3 %/oC
PI Controller design and tuning, including computing controller gain, Kc,
and reset time, Ti, from FOPDT model parameters is
summarized in
the example in this article. Following those details:
| PI
algorithm: |
 |
TRIAL
3: Moderate PI
Moderate Tc =
the larger of 1·Tp or 8·Өp
= larger of 1(2.3 min) or 8(0.25 min)
= 2.3 min

TRIAL
4: Aggressive PI
Aggressive
Tc = the larger of 0.1·Tp or 0.8·Өp
= larger of 0.1(2.3 min) or 0.8(0.25 min) = 0.23 min

|
The "step 1 data set" model parameters and the four inner secondary
controllers designed from this data are summarized in the upper half
of the table below:
Outer Primary Controller
5) We normally would implement one inner secondary
controller and test it for acceptable performance. Here, we "accept" each of the four trial
controllers and turn our attention to the outer primary loop.
The four inner secondary controllers are thus implemented one after the
other in a series of studies. When in automatic mode, each literally becomes part of the overall
process. And because each is different, we must perform four separate bump
tests and compute four sets of FOPDT model parameters to describe the four
different outer primary (overall) dynamic process behaviors.
Recall that the output of the outer primary controller output, CO1,
becomes the set
point of the inner secondary controller, SP2. Thus, bumping CO1 is the same
as bumping SP2 (i.e., CO1=SP2).
With each of the four inner secondary trial controllers in automatic, we choose to bump CO1=SP2 from 73.4 oC ®
76.4 oC ® 70.4 oC ®
73.4 oC. We again use
commercial software to fit a FOPDT dynamic model to the CO1=SP2 ®
PV2 dynamic response data sets as shown in the plots below (click
for a large view). The FOPDT model parameters (Kp, Tp,
Өp) from each bump test fit are summarized in the table above.

Industry practitioners, when designing a strategy for an application as
challenging as reactor temperature control, generally seek a moderate
response performance. Integral action will always be included to eliminate
offset issues. Thus, we pair each inner secondary trial controller with a
moderately tuned outer primary PI controller.
Following the identical procedure detailed in
trial 3 of step 4 above, we compute four
sets of moderate PI
controller tuning parameters (one for each inner secondary controller). These are listed in the last row
of the above table.
Compare Disturbance Rejection Performance
6) With both controllers in automatic, design and implementation of
the cascade is complete. The objective of this cascade is to minimize the
disruption to primary process variable PV1 when
disturbance D changes.
The specific D of concern in this study is that
the temperature of cooling liquid entering the jacket, normally at 43 oC,
is known to spike occasionally to 50 oC.
The lower trace in the plot below (click for a large view)
shows disturbance steps (temperature changes) from 43 oC up to 50 oC
and back. There are four trials shown, one for each of the inner secondary
and outer primary controller pairs listed in the table above.
The middle portion of the plot shows the constantly moving inner
secondary SP2=C01 in gold and the ability of early warning PV2
to track this ever-changing set point in black.
Recall that offset for
early warning variable PV2 is not a concern in many cascade implementations.
Here, for example, PV2 is cooling liquid temperature and cooling liquid is
not a product destined for market. So our central focus is on how control
actions based on this early warning variable help us minimize disturbance
disruptions to PV1 and not on how precisely PV2 tracks set point.

Our success is shown on the upper portion of the plot. The
outer primary set point, SP1 (in gold) remains constant throughout the
study. Our interest is in the ability of each of the cascade implementations
to maintain reactor exit temperature PV1 at SP1 in spite of the abrupt disturbance
changes.
Some Observations
In general, a more successful (or "better") cascade performance is one
where:
▪ there is a smaller maximum deviation from set point during the disturbance,
and
▪ PV1 most rapidly returns to and settles out at set point after a
disturbance.
·
Trials 2 and 4 both have aggressively tuned inner secondary controllers,
and these two implementations both have the smallest deviations from set
point and settle most rapidly back to SP. This supports the notion that
inner secondary controllers should energetically attack early warning PV2
disruptions for best cascade performance.
·
While an aggressively tuned inner secondary P-Only and PI controller
(trials 2 and 4) performed with similar success, the moderately tuned inner
secondary PI controller (trial 3) displayed markedly degraded performance.
This high sensitivity to inner loop PI tuning strengthens the "use P-Only"
conclusion made in step 3 of our cascade implementation recipe.
Comparing Cascade to Single Loop
The central question is whether the extra effort associated with cascade
control provides sufficient payoff in the form of improved disturbance
rejection performance.
To the left in the plot below (click for a large view)
is the performance of our trial 2 cascade implementation. The performance of
an aggressively tuned single loop PI controller (design
details
in this article) in rejecting the same disturbance is shown to the
right.

The cascade architecture reduces the maximum
deviation from SP during the disturbance from ±2 oC for the
single loop controller down to ±0.5
oC for the cascade. Settling time is shortened from about 10 minutes
for the single loop controller down to about 8
minutes for the cascade.
If the financial return from such improved performance is greater
than the cost to install and maintain the cascade, then choose cascade
control.
Set Point Tracking Performance
While not our design objective, presented below is the set point tracking performance
of the four cascade implementations (click for a large view):

Cascade control is best suited for improved disturbance rejection. As
shown above, its impact on set point tracking performance is minimal. While
one might argue that our "best" cascade design for disturbance
rejection (trial 2) also provides the most rapid SP tracking response, this
same improvement can be obtained with more aggressive tuning of a single
loop PI controller.
Return to the
Table of Contents to learn more.